Schneider Electric
ريلاى حماية غرف المصاعد ارتفاع وانخفاض السرعة Speed Control
- SKU:
- RM35S0MW
- الشحن والتسليم:
- الشحن خلال الفترة من 2-3 ايام عمل بخلاف ايام الاحد والعطلات الرسمية
- تغليف كهدية
- اختيارات متوفرة
الوصف
range of product |
Zelio Control
|
|
---|---|---|
product or component type |
Modular measurement and control relays
|
|
relay type |
Speed control relays
|
|
relay name |
RM35S
|
|
relay monitored parameters |
Overspeed
Underspeed |
|
time delay range |
0.6...60 s adjustable on energisation delay (tolerance: 0...10 % of the full scale value)
|
|
switching capacity in VA |
1250 VA
|
|
minimum switching current |
10 mA at 5 V DC
|
|
[Us] rated supply voltage |
24...240 V AC/DC
|
|
maximum power consumption in VA |
5 VA AC
|
|
measurement range |
0.05...0.5 s
0.5...5 min 1...10 min 1...10 s 0.5...5 s 0.1...1 s 0.1...1 min |
|
utilisation category |
AC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1 AC-14 conforming to IEC 60947-5-1 AC-15 conforming to IEC 60947-5-1 DC-12 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 DC-14 conforming to IEC 60947-5-1 |
rest time in memory mode |
50 ms contact S2 in memory mode on time delay
1 s supply Un in memory mode on time delay |
|
---|---|---|
maximum switching voltage |
250 V AC/DC
|
|
supply voltage limits |
20.4…264 V AC/DC
|
|
maximum power consumption in W |
3 W DC
|
|
width |
35 mm
|
|
output contacts |
1 C/O
|
|
contacts material |
Cadmium free
|
|
nominal output current |
5 A
|
|
delay at power up |
0.05 s
|
|
hysteresis |
5 % of threshold
|
|
measurement accuracy |
+/- 10 % of the full scale value
|
|
repeat accuracy |
+/- 0.5 % for input and measurement circuit
+/- 0.5 % for time delay |
|
measurement error |
+/- 0.1 %/°C with temperature variation
< +/- 1 % over the whole range with voltage variation |
|
input frequency |
0.0017…20 Hz
|
|
response time |
15 ms max (on crossing the threshold)
|
|
polarity |
Reversible polarity on DC supply
|
|
threshold setting |
10...100 %
|
|
supply voltage for sensor |
11.5...12.5 V
|
|
maximum supply current for sensors |
40 mA for < 24 V AC at 25 °C
40 mA for < 24 V DC at 25 °C 50 mA for 24...240 V AC 50 mA for 24...240 V DC |
|
impulse duration |
>= 5 ms high state
>= 5 ms low state |
|
input compatibility |
3-wire sensor (E1) PNP or NPN, 12 V, 50 mA
NAMUR sensor (E2), 12 V, 1.5 kOhm Voltage input (E1), 0...30 V, 9.5 kOhm, high state >= 4.5 V low state <= 1 V Volt-free contact input (E1), 12 V, 9.5 kOhm |
|
marking |
CE : EMC 89/336/EEC
CE : 73/23/EEC |
|
overvoltage category |
III conforming to IEC 60664-1
|
|
insulation resistance |
> 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5
> 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1 > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5 > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1 > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5 > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1 |
|
[Ui] rated insulation voltage |
250 V conforming to IEC 60664-1
|
|
operating voltage tolerance |
- 15 % + 10 % Un
|
|
supply frequency |
50/60 Hz +/- 10 %
|
|
operating position |
Any position without derating
|
|
connections - terminals |
Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end |
|
tightening torque |
0.6…1 N.m conforming to IEC 60947-1
|
|
housing material |
Self-extinguishing plastic
|
|
status LED |
1 LED green for power ON
1 LED yellow for inhibit 1 LED yellow for relay (R) |
|
mounting support |
35 mm symmetrical DIN rail conforming to EN/IEC 60715
|
|
electrical durability |
100000 cycles
|
|
mechanical durability |
30000000 cycles
|
|
operating rate |
<= 360 operations/hour full load
|
immunity to microbreaks |
50 ms
|
|
---|---|---|
electromagnetic compatibility |
Emission standard for industrial environments conforming to EN/IEC 61000-6-4
Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3 Immunity for industrial environments conforming to NF EN/IEC 61000-6-2 |
|
standards |
NF EN 60255-6
IEC 60255-6 |
|
product certifications |
C-Tick
GOST UL GL CSA |
|
ambient air temperature for storage |
-40…70 °C
|
|
ambient air temperature for operation |
-20…50 °C
|
|
relative humidity |
95 % at 55 °C conforming to IEC 60068-2-30
|
|
vibration resistance |
0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1
1 gn (f= 57.6…150 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1 |
|
shock resistance |
15 gn for 11 ms conforming to IEC 60255-21-1
|
|
IP degree of protection |
IP20 (terminals) conforming to IEC 60529
IP30 (casing) conforming to IEC 60529 |
|
pollution degree |
3 conforming to IEC 60664-1
|
|
dielectric test voltage |
2 kV AC 50 Hz
|
|
non-dissipating shock wave |
4 kV
|
Unit Type of Package 1 |
PCE
|
|
---|---|---|
Number of Units in Package 1 |
1
|
|
Package 1 Weight |
134 g
|
|
Package 1 Height |
4.8 cm
|
|
Package 1 width |
7.8 cm
|
|
Package 1 Length |
9.7 cm
|
|
Unit Type of Package 2 |
S03
|
|
Number of Units in Package 2 |
48
|
|
Package 2 Weight |
7.181 kg
|
|
Package 2 Height |
30 cm
|
|
Package 2 width |
30 cm
|
|
Package 2 Length |
40 cm
|