GENERAL
These luminaires are used indoors (ta 40oC)
where emergency light is needed.
Each luminaire must be permanently
connected to mains power supply.
In normal operation the led strip lights and the
battery is charging.
In case of a mains power supply failure
the luminaire will light the led strip
automatically in emergency mode (powered
by its battery). When the mains power
supply is restored the device turns to normal
operation.
INSTALLATION
To install the illumination sign you must
follow the installation instructions on pages
3,4,5 and 6.
NON MAINTAINED / MAINTAINED
OPERATION
There is an option to select the non maintained
or maintained operation by placing the jumper to
the appropriate place according to the selection
معلومات اضافية
Main Voltage: |
220-240V AC/50-60Hz |
MAXIMUM POWER CONSUMPTION: |
3.5W / 3.7VA |
BATTERY (Ni-Cd): |
3.6V/1.0Ah |
BATTERY PROTECTION: |
Overcharging and deep discharging protection |
INDICATIONS/ CONTROL: |
Charge LED / Test button |
RECHARGING TIME: |
24h |
MINIMUM EMERGENCY DURATION: |
3h |
LIGHT SOURCE INTENSITY (230V) / (emerg.): |
45lm / 95lm |
VIEWING DISTANCE: |
30m |
DEGREES OF COVER PROTECTION: |
IP40 |
PRODUCED IN ACCORDANCE WITH: |
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3, EN 1838 |
OPERATION TEMPERATURE RANGE: |
5 to 40 oC |
RELATIVE HUMIDITY: |
Up to 95% |
CONSTRUCTION MATERIALS: |
Aluminum, plexiglas, ABS/PC |